46
JOHNSON CONTROLS
5276178-JIM-C-0118
Installation
AIRFLOW
(CFM)
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2
3.4
3.6
3.8
4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
6000
916
7.4
940
7.9
964
8.3
988
8.8
1011
9.3
7000
928
8.6
953
9.1
977
9.6
1000
10.1
1023
10.7
8000
941
9.8
965
10.3
989
10.9
1013
11.5
1035
12.0
9000
952
11.2
976
11.8
1000
12.4
1023
13.0
1045
13.6
10000
964
12.6
987
13.2
1010
13.9
1033
14.5
1055
15.1
11000
981
14.1
1003
14.8
1025
15.5
1047
16.1
1069
16.8
12000
997
15.7
1019
16.4
1040
17.1
1061
17.8
1082
18.5
13000
1017
17.9
1038
18.6
1058
19.4
1078
20.1
1097
20.8
14000
1037
20.2
1056
20.9
1076
21.6
1094
22.4
1113
23.1
15000
1059
22.6
1078
23.3
1097
24.1
1115
24.9
1134
25.7
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
Refer to Table 17 for component additions and deductions to fan performance tables.
3. BHP includes drive losses.
4. Shaded RPMs require Class II blower.
TABLE 15 - FAN PERFORMANCE - 30 TON (CONT'D)
1,2
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...