196
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
DSP_RST_BAS
DUCT STATIC
PRES RST BAS
R/W
AV05
1030
A BAS ENTERED VALUE THAT RESULTS IN A
%RESET DOWN FROM THE DUCT STATIC HIGH
LIMIT BASED ON A PERCENT OF THE DIFFERENCE
BETWEEN DUCT STATIC HIGH LIMIT AND DUCT
STATIC LOW LIMIT (%). “DUCT PRES RST BAS”
MUST BE ENABLED USING THE SERVICE KEY IN
ORDER TO USE THIS FEATURE
ECON_ME_USED
ECONOMIZER
METHOD
R
AI18
531
THE ECONOMIZER METHOD BEING USED BY THE
CONTROL (1 - DRY BULB; 2 - SINGLE ENTHALPY;
3 - DUAL ENTHALPY; 4 - BEST METHOD)
ECON_STATUS
ECONOMIZER
SUITABLE ECON
INSTALLED
R
AI19
532
STATUS OF THE ECONOMIZER OPTION (0 -
INSTALLED AND INACTIVE; 1 - INSTALLED AND
ACTIVE; 2 - NOT INSTALLED; 3 - DISABLED)
ECONO_INSTAL
ECONOMIZER
INSTALLED
R/W
AV81
1106
ALLOWS THE ECONOMIZER FEATURE TO BE
TURNED ON AND OFF (0 = OFF / 1 = ON)
ECONO_METHOD
ECONOMIZER
METHOD
R/W
AV06
1031
THE ECONOMIZER METHOD SELECTED FOR USE
(1 - DRY BULB; 2- SINGLE ENTHALPY; 3 - DUAL
ENTHALPY; 4 - BEST METHOD)
EL_AIR_TMP_H
EVAP LEAVING AIR
TEMP HIGH
R/W
AV07
1032
ON A FLEXSYS UNIT WITH BYPASS THIS IS THE
SUPPLY AIR TEMPERATURE HIGH SET POINT (F)
EL_AIR_TMP_L
EVAP LEAVING AIR
TEMP LOW
R/W
AV08
1033
ON A FLEXSYS UNIT WITH BYPASS THIS IS THE
SUPPLY AIR TEMPERATURE LOW SET POINT (F)
EVAP_AIR_TMP
EVAPORATOR AIR
TEMP 1
R
AI20
533
ACTUAL TEMPERATURE OF AIR LEAVING THE
EVAPORATOR COIL ON A FLEXSYS UNIT (F)
EXH_FAN_STAT
EXHAUST FAN
STATUS
R
BI21
1302
THE STATUS OF THE EXHAUST FAN RUN
VERIFICATION CIRCUIT (0 - VERIFICATION CIRCUIT
OPEN / 1 - VERIFICATION CIRCUIT CLOSED)
EXHAUST_FAN
EXHAUST FAN
R
BI22
1303
THE STATUS OF THE BINARY OUTPUT FOR THE
EXHAUST (0 = OFF / 1 = ON)
EXHAUST_OUT
EXHAUST OUTPUT
R
AI21
534
CONTROL OUTPUT TO THE EXHAUST DAMPER (%)
FAN_FAULT
FAN FAULT
R
BI23
1304
IDENTIFIES IF THERE IS A SUPPLY, EXHAUST, OR
RETURN FAN FAULT (0 - NO FAULT; 1 - FAULTED)
FAN_G
FAN(G)
R
BI24
1305
IDENTIFIES WITH THE UNIT HAS A BINARY FAN (G)
INPUT EITHER HARWIRED OR COMMUNCIATED
(ON / OFF)
FAN_G_BAS
FAN (G) BAS
R/W
AV(BV)82
1107
A COMMUNICATED INPUT THAT ALLOWS THE (G)
FAN INPUT TO BE TURNED ON AND OFF (0 = OFF;
1 = ON)
FILTER_STATS
FILTER STATUS
R
BI25
1306
IDENTIFIES THE STATUS OF THE BINARY DIRTY
FILTER INPUT (0 - NO FAULT; 1 - FAULTED)
FURN_OUT_1
ELECTRIC HEAT
STAGE 1 STG GAS
FURNACE 1
R
BI26
1307
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
FURN_OUT_2
ELECTRIC HEAT
STAGE 2 STG GAS
FURNACE 1 HIGH
R
BI27
1308
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
FURN_OUT_3
ELECTRIC HEAT
STAGE 3 STG GAS
FURNACE 2 LOW
R
BI28
1309
INDICATES THE STATUS OF THE BINARY OUTPUT
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...