210
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
ACT _DSP_SP
DUCT STATIC SET
POINT
R
AI01
WC
AI 1
A DERIVED VALUE THE DUCT STATIC IS
CONTROLLED TO (“WG)
ACT_MIN_
FLOW
ACTIVE MINIMUM
AIR FLOW
R
AI02
CFM
AI 2
THIS FEATURE IS NOT AVAIL-
ABLE ON THIS UNIT.
ACT_MIN_POS
ACTIVE MINIMUM
POSITION
R
AI03
%
AI 3
A DERIVED VALUE THE DAMPER IS CONTROLLED
TO FOR MINIMUM VENTILATION AIR (%)
ACT_SAT_SP
SUPPLY AIR SETP
R
AI04
DEG F
AI 4
A DERIVED VALUE THE SUPPLY AIR
TEMPERATURE IS CONTROLLED TO (F)
ACT_SLAB_
CTL
ACTIVE SLAB
CONTROL
R/W
AV77
0, 1
AO 34
ALLOWS THE ACTIVE SLAB CONTROL FEATURE
TO BE TURNED ON AND OFF ON FLEXSYS UNITS
(0 = OFF / 1 = ON)
BUILD_PRES_
SP
BUILDING
PRESSURE SP
R/W
AV01
WC
AO 1
THE BUILDING PRESSURE SET POINT (“WG)
BLD_STAT_
PRS
BUILDING STATIC
PRES
R
AI05
WC
AI 5
ACTUAL BUILDING PRESSURE INPUT (“WG)
BYPASS_
DAMPER
BYPASS DAMPER
R
AI06
%
AI 6
ACTUAL BYPASS DAMPER POSITION (%)
CO
2
_1_OUT
CO
2
1
(OUTSIDE)
R
AI07
PPM
AI 7
ACTUAL
OUTDOOR
CO
2
VALUE
(PPM)
C02_2_INSIDE CO
2
1 (INSIDE)
R
AI08
PPM
AI 8
ACTUAL INDOOR CO
2
VALUE (PPM)
CO
2
_OFFSET
CO
2
OFFSET
R/W
AV02
PPM
AO 2
THE DIFFERENCE BETWEEN THE INDOOR AND
OUTSIDE CO
2
MUST EXCEED THIS VALUE TO
INITIATE DEMAND VENTILATION (PPM)
COL_HEAT_
FLT
COOLING/
HEATING FAULT
R
BI02
0, 1
DI 1
GIVES THE FAULT STATUS OF THE COOLING
AND HEATING SYSTEM (NFL - NO FAULT; FLT -
FAULTED)
COMP_1A
COMPRESSOR 1A
R
BI03
0, 1
DI 2
STATUS OF COMPRESSOR 1 (0 = OFF, 1 = ON)
COMP_1B
COMPRESSOR 1B
R
BI04
0, 1
DI 3
STATUS OF COMPRESSOR 2 (0 = OFF, 1 = ON)
COMP_2A
COMPRESSOR 2A
R
BI05
0, 1
DI 4
STATUS OF COMPRESSOR 3 (0 = OFF, 1 = ON)
COMP_2B
COMPRESSOR 2B
R
BI06
0, 1
DI 5
STATUS OF COMPRESSOR 4 (0 = OFF, 1 = ON)
COMP_3A
COMPRESSOR 3A
R
BI07
0, 1
DI 6
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
COMP_3B
COMPRESSOR 3B
R
BI08
0, 1
DI 7
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
COMP_LPCO_1
COMPRESSOR
LPCO 1
R
BI09
0, 1
DI 8
STATUS OF COMPRESSOR 1 or 2 LOW PRESSURE
CUTOUT CIRCUIT (0 - FAULTED / 1 - NO FAULT )
COMP_LPCO_2
COMPRESSOR
LPCO 2
R
BI10
0, 1
DI 9
STATUS OF COMPRESSOR 3 or 4 LOW PRESSURE
CUTOUT CIRCUIT (0 - FAULTED / 1 - NO FAULT )
TABLE 92
-
N2 POINTS LIST
(See notes at end of table)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...