MENU ITEM
DEFINITION
SUPPLY SYS STATUS
This is the active status of the Supply System, display will show Normal- Active;
Normal-Inactive; Safety Trip, Safety Fault, or Safety Lockout.
SYSTEM UNLOADING PRESSURE
This parameter is programmed through the SETPOINTS key. If two compressors
of the system are operative and the discharge pressure is equal to or greater than
this value the Unit Controller will turn off one of the compressors. This feature is
only operative when a discharge pressure transducer is installed in the compressor
system.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
TEMPERATURE SUPERHEAT
This is calculated for each compressor system that has a suction line pressure
transducer installed and configured. This is the refrigerant evaporator superheat
leaving the evaporator coil.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
UNDERFLOOR AIR HUMIDITY
This is the humidity level under the floor of a FlexSys installation.
UNDERFLOOR AIR TEMP
This is the temperature of the air in the underfloor space.
UNDERFLOOR SLAB DEW POINT
This is the dewpoint of the air beneath the floor of a FlexSys installation.
UNDERFLOOR SLAB TEMP
This is the temperature of the slab beneath the floor of a FlexSys installation.
UNIT INSTALLED ALTITUDE
This parameter is programmed through the SETPOINTS key. This is the altitude
at which the unit is installed. This is used in the calculation of an airflow correction
factory when air measuring stations are installed.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
UNIT SIZE
This parameter is programmed through the OPTIONS key and identifies the size of
the unit. The choices are 50 Ton, 55 Ton, 60 Ton, 65 Ton, 70 Ton, 75 Ton, 80 Ton, 85
Ton, 90 Ton, 95 Ton, 105 Ton, 106 Ton, 110 Ton, 115 Ton, 130 Ton, or 150 Ton.
UNIT TYPE
This parameter is programmed through the OPTIONS key and identifies the type of
unit. The choices are Constant Volume, Variable Volume, or FlexSys.
UNIT-OVERALL STATUS
This is the active status of the Unit. The display will show Local Stop, Run, Unit Trip,
Unit Fault, Unit Lockout, SMK Purge # - Press, SMK Purge #-Purge, Smk Purge
#-Evac, or Unstable system.
VENT SYS STATUS
This is the active status of the Ventilation System. The display will show Normal-
Active, Normal-Inactive, Safety Trip, Safety Fault, Safety Lockout, User Disabled,
or None.
VENTILATION CONTROL
This parameter is programmed through the OPTIONS key and identifies whether the
unit will operate with a Fixed Minimum or Demand ventilation system.
VENTILATION DEMAND
This is the output in percent to the outside air damper when the unit is operating in
the Demand Ventilation mode.
ZONE TEMP CURRENT
This is the temperature in the conditioned space.
ZONE TEMP OCC ZONE COOLING
SETPOINT
This parameter is programmed using the SETPOINTS key. This is the temperature
that the Unit Controller compares the actual space temperature to, to decide when
to switch into the Occupied Cooling Mode.
ZONE TEMP OCC ZONE HEATING
SETPOINT
This parameter is programmed using the SETPOINTS key. This is the temperature
that the Unit Controller compares the actual space temperature to, to decide when
to switch into the Occupied Heating Mode.
ZONE TEMP UNOCC ZONE COOLING
SETPOINT
This parameter is programmed using the SETPOINTS key. This is the temperature
that the Unit Controller compares the actual space temperature to, to decide when
to switch into the Unoccupied Cooling Mode.
ZONE TEMP UNOCC ZONE HEATING
SETPOINT
This parameter is programmed using the SETPOINTS key. This is the temperature
that the Unit Controller compares the actual space temperature to, to decide when
to switch into the Unoccupied Heating Mode.
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...