This unit is not designed to be handled with a fork-
truck.
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation.
Rig the unit by attaching cable slings to the lifting lugs
provided in the unit base rails. Spreaders MUST be used
across the top of the unit.
Refer to Figure 4.
• Rig with six cables and spread with three 95-inch
spreaders across width of unit.
• Center of gravity includes economizer, exhaust or
return air fan and inlet guide vanes
(Refer to Table
7).
If a unit is to be installed on a roof curb
other than a Johnson Controls roof
curb, gasketing must be applied to all
surfaces that come in contact with the
unit underside.
If a unit is to be installed on an angle
iron frame it is recommended that it
be sized to allow the bottom rail to
overhang to facilitate installation of
condensate drains (see Figures 24
and 25).
TABLE 7 - UNIT CENTER OF GRAVITY
LD14170A
FIGURE 4 - TYPICAL RIGGING
NOTICE TO RIGGERS
(1) RIG WITH SIX CABLES AND THREE SPREADER BARS AT
(2) CENTER OF GRAVITY INCLUDES ECONOMIZER, POWER
EXHAUST AND INLET GUIDE VANES.
(3) AFTER UNIT IS IN PLACE, INSTALL COVER PLATE OVER
RIGGING HOLES ON POWER EXHAUST END.
LEAST 95” ACROSS THE WIDTH OF THE UNIT.
CABLES
SPREADER BARS
SPREADER BAR
1. Rig with six cables and three spreader bars at
least 95" across width of the unit.
2. Center of gravity includes economizer, power
exhaust and inlet guide vanes.
3. After unit is in place, install cover plate over
rigging holes on power exhaust end.
NOTICE TO RIGGERS
MODEL
25 TON
30 TON
40 TON
X
Y
X
Y
X
Y
BASIC UNIT
99”
48”
97”
46”
98”
46"
BASIC UNIT /W ECON.
110” 48” 107” 46” 102” 46"
BASIC UNIT /W ECON. & GAS OR ELECT. HEAT, STEAM OR HOT WATER HEAT
104” 48” 101” 47” 101” 47"
BASIC UNIT /W ECON. & GAS OR ELECT. HEAT, & POWER EXHAUST
118” 47” 111” 47” 113” 47"
TABLE 8 - UNIT WEIGHTS
COMPONENT
25 TON
30 TON
40 TON
BASIC UNIT
4410
4605
4785
GAS HEAT
267 MBH
180
180
180
533 MBH
320
320
320
800 MBH
-
-
450
ELECTRIC HEAT
40KW
40
40
40
80KW
105
105
105
108KW
110
110
110
HOT WATER HEAT
1 ROW COIL
70
70
70
2 ROW COIL
85
85
85
STEAM HEAT
1 ROW COIL
85
85
85
BLOWER
FORWARD
CURVE FAN
(STD FAN)
0
0
0
FC IGV
155
155
175
AIR FOIL FAN
135
135
155
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...