Installation
For all hot water coils the entering
water temperature should not exceed
200°F.
The hot water coil is located downstream of the supply
air fan and just above the supply air opening in the
bottom of the unit.
Refer to Tables 43 through 51 and Figure 34 through
47 for flow rate and capacity.
There are no provisions in the coil or
control sequence to prevent freezing of
condensate. The control valve, piping
and field installed wiring connections
are particularly vulnerable because
they are installed in the vestibule
outside of the conditioned air stream.
The installing party will be responsible
for properly insulating and installing
power and control wiring, to the actua
-
tor and piping.
In one row hot water coil systems DO
NOT exceed 40 gallons per minute
flow rate.
In two row hot water coil systems DO
NOT exceed 80 gallons per minute
flow rate.
Condensate will freeze on the control
valve and piping if they are not prop
-
erly insulated. Insulating the control
valve and piping is the responsibility
of the installing party.
Piping Connections
The hot water piping must enter the unit through the
floor of the heat section compartment. The access doors
to the compartment are gasketed so the compartment
can be sealed. However, as added protection for water
leakage into the space, the piping access holes should
be sealed with a heat resistant mastic.
Figure 31 shows
the location of the compartment and piping connections
.
Piping access holes should be sealed
with a heat resistant mastic to prevent
damage to equipment.
DO NOT use tin based solder. Braz
-
ing with tin based solder could cause
equipment damage or possible injury
to tenants of the structure that is being
conditioned.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...