TABLE 102 - FAULT AUTO - RESET
HISTORY
SCREEN
WORDING
DESCRIPTION
RESET
HOW WHEN UNIT
TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
AUTO RESET-
COMPRESSOR
SYSTEM *
CLEAR
SEE DESCRIPTION BELOW
AUTO
RESET
AUTO RESET-
COMPRESS
SYSTEM *
TRIP 1
THE SAFETY INPUT CHAIN IS OPEN
(FAULTED) FOR MORE THEN TWO
SECONDS WITH EITHER OR BOTH
COMPRESSOR OF THE SYSTEM ON AND
THIS IS THE FIRST TRIP IN A 120 MINUTE
SPAN
AUTO
RESET
COMP
SYSTEM
* STATUS
SAFVETY
TRIP
COOLING
HEATING
FAULT
AUTO RESET
COMPRESSOR
SYSTEM *
TRIP 2
THE SAFETY INPUT CHAIN IS OPEN
(FAULTED) FOR MORE THEN TWO
SECONDS WITH EITHER OR BOTH
COMPRESSOR OF THE SYSTEM ON
AND THIS IS THE SECOND TRIP IN A 120
MINUTE SPAN
AUTO
RESET
COMP
SYSTEM
* STATUS
SAFETY TRIP
COOLING
HEATING
FAULT
AUTO RESET -
MSAT SENSOR
MS SUPPLY AIR TEMP CURRENT
SENSOR IS OUT OF RANGE FOR MORE
THAN OR EQUAL TO 10 SECONDS.
AUTO
RESET
UNIT TYPE IS
FLEXSYS
SENSOR/
MISC STATUS
SAFETY
LOCKOUT
SENSOR/
MISC
FAULT
AUTO RESET -
POWER FAIL
POWER IS LOST WHEN THE UNIT
OPERATING STATE IS RUN
AUTO
RESET
AUTO RESET -
RAT SENSOR
RETURN AIR TEMP CURRENT SENSOR
IS OUT OF RANGE FOR MORE THAN OR
EQUAL TO 10 SECONDS
AUTO
RESET
SENSOR/
MISC STATUS
SAFETY
FAULT
SENSOR/
MISC
FAULT
AUTO RESET
- REMOTE I/O
COMM
NO COMMUNICATION FROM THE I/O
BOARD FOR MORE THAN OR EQUAL TO
5 SECONDS
AUTO
RESET
SENSOR/
MISC
FAULT
AUTO RESET
- STAGED
INPUT
THE CONTROL HAS A COOLING AND
HEATING THERMOSTAT INPUT AT THE
SAME TIME FOR A PERIOD GREATER
THAN 10 SECONDS
AUTO
RESET
SENSOR/
MISC STATUS
SAFETY
LOCKOUT
SENSOR/
MISC
FAULT
AUTO RESET
- ZONE TEMP
SENSOR
ZONE TEMP CURRENT SENSOR IS OUT
OF RANGE FOR MORE THAN OR EQUAL
TO 10 SECONDS
AUTO
RESET
UNIT TYPE IS VAV
AND NIGHT SET
BACKIS USER
ENABLED OR
UNIT TYPE IS
SET TO CV AND
THE CONTROL
METHOD IS
SET TO ZONE
SENSOR
HARDWIRED
SENSOR/
MISC STATUS
SAFETY
LOCKOUT
SENSOR/
MISC
FAULT
* CAN BE 1, 2, OR 3
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...