49
2
JOHNSON CONTROLS
5276178-JIM-C-0118
AIRFLOW
(CFM)
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2
3.4
3.6
3.8
4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
8000
780
8.6
800
9.2
821
9.9
841
10.5
861
11.2
9000
790
9.8
811
10.5
831
11.1
852
11.8
872
12.5
10000
801
11.0
821
11.7
842
12.3
862
12.9
882
13.6
11000
809
12.2
831
12.8
850
13.5
871
14.2
890
14.9
12000
819
13.2
839
14.0
859
14.7
879
15.4
899
16.1
13000
828
14.7
848
15.4
868
16.2
887
17.0
907
17.7
14000
839
16.0
858
16.8
878
17.6
896
18.4
915
19.2
15000
850
17.7
870
18.5
889
19.3
907
20.1
926
21.0
16000
863
19.3
882
20.2
900
21.1
918
22.0
936
22.8
17000
877
21.3
896
22.2
913
23.1
931
23.8
944
24.6
18000
891
23.3
910
24.2
928
25.1
946
26.1
-
-
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
Refer to Table 17 for component additions and deductions to fan performance tables.
3. BHP includes drive losses.
4. Shaded RPMs require Class II blower.
TABLE 16 - FAN PERFORMANCE - 40 TON (CONT'D)
1,2
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...