161
JOHNSON CONTROLS
5276178-JIM-C-0118
6
When a numeric value that can be modified is displayed,
the Default, High, and Low prompt will be shown in
the upper right portion of the display. The cursor will
be shown at the digit to be changed. The cursor will
be shown after editing has started. After the desired
numeric value has been entered, press the
key to
save the new value and exit the edit mode. Pressing
the ◄ key will fill in the default value. Edits will only
be accepted when followed by pressing the
key.
Pressing the
X
key while in the edit mode will cancel
the edit mode and leave the value unchanged. If an out
of range value is entered, the Default, High and Low
prompt is replaced by the “Out of Range” message for
two seconds.
When a choice value that can be modified is displayed,
the ◄ ► prompt will be shown in the upper right portion
of the display. The cursor will be shown after editing
has been started. The ◄ key or the ► key will allow
the different choices to be viewed. When the desired
choice is displayed, press the
key to save the new
value and exit the edit mode. Pressing the
X
key while
in the edit mode will cancel the edit mode and leave the
value unchanged.
Navigation Keys
The Navigation Keys provide a means to browse items
within a menu. The keys currently available to support
navigation are the Menu Select keys, the ▲ key, the ▼
key, the ◄ key, and the ► key.
Pressing a Menu Select key brings the user to the first
screen under that menu. The screens within each menu
are arranged in a circular list. The user may browse
through the screens using the ▲ key and the ▼ key.
Pressing the ▼ key will advance through the screens
in order from top to bottom until the bottom screen has
been reached. When the bottom screen is displayed,
pressing the ▼ key will wrap the display to the top
screen of the menu. Pressing the ▲ key will move
through the screens in order from bottom to top until
the top screen has been reached. When top screen is
displayed, pressing the ▲ key will wrap the display to
the bottom screen of the menu. Once either the ▲ key
or the key ▼ is pressed, pressing any Menu Select key
will bring the user to the first screen under that menu
(even if it is the same menu being viewed).
Navigation through the circular list of items can also be
achieved by repeated presses of the same Menu Select
key, as long as no other keys are pressed. For example,
pressing the UNIT DATA key three times will bring
the user to the third screen of the UNIT DATA menu;
pressing the UNIT DATA key once, then pressing the ▼
key, then pressing the UNIT DATA key again will bring
the user to the first screen of the UNIT DATA menu.
The ◄ key and the ► key are used to scroll “sideways”
between the same displays for each system. For
example, when viewing the Sys 1 Pressures under the
COMPRESSOR SYSTEMS key, pressing the ► key
will scroll “sideways” to the Sys 2 Pressures display and
pressing the ◄ key will scroll “sideways” to the Sys
Pressures display for the last system on the unit.
When programming numeric or non-numeric values,
the ▼ key and the ▲ key are used to scroll forward
(down) and backward (up) through the items to be
programmed or set.
Menu Select Keys
The following menu keys are available on the User
Interface; STATUS, UNIT DATA, COOLING,
COMPRESSOR SYSTEMS, SUPPLY SYSTEM,
HEATING, ECONOMIZER, VENTILATION,
EXHAUST, SETPOINTS, PROGRAM, OPTIONS,
DATE/TIME, SCHEDULE, OPERATING HOURS
/ START COUNTER, PRINT, SERVICE, and
HISTORY.
Each of the above menu keys gives access to a list of
specific items contained in that menu. To minimize
clutter, only the items applicable to the current unit
configuration will be displayed. Pressing any of the
menu select keys at any time will send the user to the
first item of the associated menu, provided the user is not
editing an item in the current menu key item or the menu
key is being used to navigate through a list of items.
Tables 69 through 77 list the information that is
contained under the STATUS, UNIT DATA, COOLING,
COMPRESSOR SYSTEMS, SUPPLY SYSTEM,
HEATING, ECONOMIZER, VENTILATION, and
EXHAUST menu selection keys of the User Interface.
The tables contain the Displayed Text, Pass Word Level
(if applicable), Range of Values (if applicable), Default
Value (if applicable), what key (Setpoints, Program,
Options) to use to change the value (if applicable), and
under what circumstances the item is displayed.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...