240
JOHNSON CONTROLS
5276178-JIM-C-0118
Service
TABLE 103 - FAULTS LOCKOUT
HISTORY
SCREEN
WORDING
DESCRIPTION
RESET
SHOW WHEN
UNIT TYPE IS
STATUS
SCREEN
WORDING
FAULT
OUTPUT
TYPE
LOCKOUT-
COMPRESSOR
SYSTEM * TIME
OUT
SEE BELOW
SYSTEM
LOCKOUT
COMP
SYSTEM
* - SAFETY
LOCKOUT
COOLING
HEATING
FAULT
LOCKOUT -
COMPRESSOR
SYSTEM *
HIGH PRESS SW, LOW PRESSURE
SW - 3 TIMES IN 120 MINUTES ON
COMP SYSTEM *
SYSTEM
LOCKOUT
COMP
SYSTEM
* - SAFETY
LOCKOUT
COOLING
HEATING
FAULT
LOCKOUT-
HIGH DUCT
PRESSURE
DUCT STATIC PRESS CURRENT
.PLUS DUCT STATIC OVER
PRESSURE
UNIT
LOCKOUT
UNIT TYPE IS
VAV OR FLEXSYS
SUPPLY
SYS STATUS
SAFETY
LOCKOUT
FAN
FAULT
LOCKOUT - HOT
WATER FREEZE
THE HYDRONIC FREEZE STAT
SWITCH REMAINED CLOSED MORE
THAN OR EQUAL TO 5 MINUTES
UNIT
LOCKOUT
HEAT TYPE HOT
WATER / STEAM
HEATING
SYS STATUS
- SAFETY
LOCKOUT
COOLING
HEATING
FAULT
LOCKOUT -
MANUAL STOP *
THE COMPRESSOR SYSTEM
HAS BEEN PLACED IN THE
STOP MODE EITHER THROUGH
THE USER INTERFACE OR BY A
COMMUNICATED INPUT
SYSTEM
LOCKOUT
COMP SYS
* STATUS
DISABLED
LOCKOUT -
MANUAL UNIT
STOP
THE UNIT IS SHUT DOWN
THROUGH THE SHUT DOWN
SWITCH ON THE UNIT OR BY
AN EXTERNAL HARDWIRED OR
COMMUNICATED INPUT
UNIT
LOCKOUT
UNIT -
OVERALL
STATUS
LOCAL STOP
LOCKOUT - OAT
SENSOR
OUTSIDE AIR TEMP SENSOR IS OUT
OF RANGE FOR MORE THAN OR
EQUAL TO 10 SECONDS
UNIT
LOCKOUT
COMP SYS
* STATUS
SAFETY
LOCKOUT;
ECONO SYS
STATUS
SAFETY
LOCKOUT
SENSOR/
MISC
FAULT
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...