JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 81 - COOLING
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
SUPPLY AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR VOLUM
ACTIVE SP
50.0º F TO 150.0º F
DERIVED
FLEX EVAP TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS FLEXSYS AND
CURRENT OPER MODE IS OCC
COOLING W/ BYP
ACTIVE SP
50.0º F TO 60.0º F
DERIVED
MX SUPPLY AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS FLEXSYS
SETPOINT
1
50.0º F TO 75.0º F
65.0º F
SETPOINTS/
COOLING
COOLING CONTROL
OFFSET
1.0º F TO 100.0º F
DERIVED
RETURN AIR DIFF SP
2
2.0º F TO 10.0º F
6.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS FLEXSYS
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR VOLUM
OCC ZONE COOLING
SETPOINT
1
OCC ZONE H
2.0º F TO 85.0º F
72.0º F
SETPOINTS/
COOLING
ZONE TEMP*
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS CONSTANT
VOLUME OR VARIABLE AIR VOLUM
UNOCC ZONE
COOLING
SETPOINT
1
UNOCC ZONE
H 2.0º F TO
95.0º F
85.0º F
SETPOINTS/
COOLING
RETURN AIR TEMP
CURRENT
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
RAT COOLING
SETPOINT
1
RAT HEATING SETP
+2º F TO RAT FOR
HIGH SAT
70.0º F
SETPOINTS/
COOLING
RETURN AIR BYPASS
CURRENT
0 TO 100%
DERIVED
UNIT TYPE EQUALS FLEXSYS
ACTIVE SP
0 TO 100%
DERIVED
BYPASS DAMPER
POSITION
0 TO 100%
DERIVED
UNIT TYPE EQUALS FLEXSYS
UNDERFLOOR AIR
TEMP
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS FLEXSYS
AND DEWPOINT RESET EQUALS
ENABLED
HUMIDITY
0 TO 100%
DERIVED
UNDERFLOOR SLAB
TEMP
-20.0º F TO 180.0º F
LOOK UP TABLE
UNIT TYPE EQUALS FLEXSYS
AND DEWPOINT RESET EQUALS
ENABLED
DEW POINT
30.0º F TO 100.0º F
DERIVED
MAXIMUM BYPASS
1
20.0 TO 40.0%
40%
SETPOINTS/
COOLING
UNIT TYPE EQUALS FLEXSYS
* ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN.
Содержание 40 25 TON
Страница 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Страница 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Страница 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...