3.3.5 Installing Water Pipes
The designed height of the water trap must meet the requirements specified in
.
Figure 3-11 Designed height of the water trap
NO TE
It is recommended that the height of segment B be a smaller value.
Installing Water Pipes
NO TICE
● Ensure that the external pipes are clean and free from foreign matter before
connecting to the water inlet and outlet pipes. Do not let external impurities
enter the pipes.
● The water inlet and outlet pipes of the unit are connected using screw threads.
Do not exert excessive force when connecting the pipes to avoid damaging the
pipes. (Use two pipe pliers or chain pliers to connect pipes.)
Water pipes need to be prepared onsite. If galvanized steel pipes are used,
stainless steel connectors must be used to ensure sealing.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 System Installation (Building Scenario)
Issue 02 (2021-04-15)