Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0-500 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 6-4 Description
Parameter
Description
Configuration Principle
Indoor fan control
type
Sets the control type for
the indoor fan.
Normally, retain R/S air
temp diff rate ctrl. If the
differential pressure sensors
are configured, change to
Pressure diff ctrl.
Indoor fan silent
mode
Set maximum speed of
indoor fan to reduce
equipment noise.
You are advised not to
change the value.
Indoor fan pressure
difference setpoint
Sets the value for the
pressure difference
control.
You are advised not to
change the value.
Air-side difference
pressure sensor type
Sets the measuring range
for the air side
differential pressure
sensor.
There is no default value. Set
it to 0-500 Pa.
Min indoor fan
speed
Sets the minimum speed
for the indoor fan.
The default value is 30%.
You are advised not to
change the value.
Max indoor fan
speed
Sets the maximum speed
for the indoor fan.
The default value is 100%.
----End
6.4.3 (Optional) Setting Teamwork Control Parameters
Prerequisites
The teamwork control numbers and addresses for teamwork controlled smart
cooling products have been set as follows:
●
Teamwork group No.: Group the smart cooling products in same aisle or
adjacent areas as one, that is, assign one teamwork group number for them.
At most four teamwork groups can be assigned (1–4).
●
System address: The address (configurable range: 1-32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual