4.4.4.3 CAN Te FE Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
Teamwork
Monitoring
Protocol
CAN
Modbus-TCP/SNMP
Description
One teamwork network
supports a maximum of 32
smart cooling products. On
the Teamwork Settings
screen of the display modules
of the first and last smart
cooling products, set Enable
teamwork CAN resistor to
Yes.
-
NO TE
Customers can purchase Huawei's switch and NetEco for the monitoring system.
Figure 4-24 Connecting communications cables
----End
4.4.4.4 FE Te RS485 Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
Teamwork
Monitoring
Protocol
MAC_CAN
Modbus-RTU
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (FDC Scenario)
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.