Figure 6-25 Wizard Startup screen
NO TE
● For the initial wizard startup, Last Record is in gray, indicating that operation is not
allowed.
● For a non-initial wizard startup, you can choose Last Record to view the last wizard
startup report.
Step 2 Tap Yes to enter the screen for checking before startup.
Figure 6-26 Checking before startup screen
Step 3 Follow the onscreen instructions to complete the wizard startup.
NO TE
● When you enter the screen for selecting commissioning items for the first time, all items
are selected by default.
● After commissioning for a component succeeds, the system automatically performs
commissioning for the next component you selected. If commissioning fails, wizard
startup ends.
----End
6.7 Power-Off
Context
In shutdown mode, the Shutdown button is green (unavailable) and the Start
button is gray (available).
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
6 Power-On Commissioning
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
128