Figure 9-6 Opening the side panel
NO TE
The position of the side panel to be removed in the FDC scenario is the same as that in the
building scenario. This example shows how to open the side panel in the FDC scenario.
Step 3 Insert the negative pressure tube of the differential pressure gauge into the unit
through the hole in the return air baffle plate of the fan for about 30 mm.
Step 4 Insert the positive pressure tube of the differential pressure gauge into the unit
through the cable hole for about 30 mm.
Figure 9-7 Pressure measurement points
(1) Pressure measurement point for the
negative pressure tube
(2) Pressure measurement point for the
positive pressure tube
NO TE
The cross section of the pressure tubes must be perpendicular to the wind direction.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
9 FAQ
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
239