Parameter
Description
Settings > System
Settings >
Compressor
Compressor*
preheating
Specifies whether to forcibly start the
preheating function of the compressor oil
heating belt.
Settings > System
Settings > Indoor
Fan
Indoor fan
control type
Set this parameter to R/S air temp diff
rate ctrl, R/S air temp diff ctrl, or
Pressure diff ctrl.
Air-side
difference
pressure
sensor type
Select the measuring range of the air-
side differential pressure sensor.
Min indoor
fan speed
Specifies the minimum rotational speed
of the indoor fan.
Max indoor
fan speed
Specifies the maximum rotational speed
of the indoor fan.
Supply air
damper
Supply air damper can be set to Enable
or Disable.
Return air
damper
Return air damper can be set to Enable
or Disable.
Settings > System
Settings > Spray
System
Spray pump
rotation
period
Specifies spray pump rotation period.
Antifreeze
temperature
Specifies the lowest temperature for the
spray system.
Settings > System
Settings > Exhaust
Fan
Min exhaust
fan speed
Specifies the minimum rotational speed
of the exhaust fan.
Max exhaust
fan speed
Specifies the maximum rotational speed
of the exhaust fan.
Exhaust air
damper
Exhaust air damper can be set to
Enable or Disable.
Settings > System
Settings >
Mainboard
Differ
pressure
switch for
outd intake
air filter
You can enable or disable the differential
pressure switch of the outdoor intake air
filter.
Preset total
system
power
consumption
Specifies the total energy consumption of
the unit.
Maint >
Performance Maint
System total
power
consumption
Display the accumulated runtime for
each component.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
268