Networking
Teamwork
Monitoring
Note
One teamwork network
supports a maximum of 16
smart cooling products.
It takes 3 x
n
seconds to
collect data from
n
smart
cooling products. If the time
required for the host to collect
data from all smart cooling
products does not meet the
performance requirements,
group the smart cooling
products.
● If devices are not grouped
(
n
= 1), set RS485
monitoring grouping to
Enable on the Modbus
Settings screen for each
device.
● If devices are grouped (
n
>
1; recommended:
n
≤ 4),
set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the device with the
COM/FE port connected.
NO TE
● Connect the COM/FE port on the main control module of the last smart cooling product
in each group to the RS485 port on the host.
● Customers can purchase Huawei's ECC and NetEco for the monitoring system.
Figure 4-25 Connecting communications cables
----End
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (FDC Scenario)
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
88