Table 8-4 Fan troubleshooting
Fault
Type
Possible Cause
Solution
The fan
does not
rotate.
Check whether the
power supply voltage
meets the
requirements.
Check the power supply voltage.
Open phase occurs.
The voltage is less
than the lower
threshold or greater
than the upper
threshold.
A short circuit exists
between the fan and
the ground.
Check the power cable and voltage of the
motor.
The coil is short-
circuited or the
motor is burnt.
Replace the fan. If there is a beam for
hoisting the fan in the air exhaust section,
before removing the fan, use a hook to
secure the fan to the beam to prevent the
fan from falling.
The overtemperature
protection function
of the motor is
triggered (the motor
is overheated).
Check whether the air circulation is normal.
Clear foreign matters if necessary.
The fan blade is blocked or dirty.
Check the ambient temperature of the fan.
Check the voltage.
The fan blade is
blocked or dirty.
Power off the motor and prevent it from
being connected again.
● Check whether the motor is powered off.
● Clear foreign matters or contaminants.
The airflow direction
is incorrect (the
direction of the
motor is opposite to
that of the high-
speed airflow).
Check the airflow direction (rotation caused
by airflow reversal).
The fan
rotates
slowly.
Fan blade friction/
collision
Clear foreign matters or dirt in the fan if
necessary.
The active
temperature
management
function is enabled
Check whether the air circulation is normal.
Clear foreign matters if necessary.
The fan blade is blocked or polluted.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
140