Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A362-01
Spray pump 1 drive
power supply
abnormal
Spray pump 2 drive
power supply
abnormal
Major
● The power supply
to the spray pump
drive is abnormal.
● The cables to the
spray pump drive
are loose or
damaged.
1. Check the power
supply to the spray
pump drive.
2. Check the cables to
the spray pump
drive.
A363-01
Spray pump 1 drive
output abnormal
Spray pump 2 drive
output abnormal
Major
● The output cables
to the spray pump
drive are loose or
damaged.
● The spray pump is
faulty.
● The spray pump
drive is faulty.
1. Check the output
cables to the spray
pump drive.
2. Maintain or replace
the spray pump.
3. Maintain or replace
the spray pump
drive.
A364-01
Spray pump 1 drive
overcurrent
Spray pump 2 drive
overcurrent
Major
● The spray pump is
faulty.
● The spray pump
drive is faulty.
1. Maintain or replace
the spray pump.
2. Maintain or replace
the spray pump
drive.
A371-01
Parts replacement
alarm
Warning
Reserved
Reserved
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
185