Symptom
Possible Cause
Solution
The interconnection
terminals for the fans are not
securely connected.
Secure the interconnection
terminals.
The water
system cannot
spray properly.
The water pump is sealed by
gas.
When the water pump of the
smart cooling product runs
for the first time every year,
the water pump may be
sealed by gas and cannot
spray properly. In this case,
you need to manually
exhaust air. When the water
pump is running, remove the
exhaust plug on the water
pump. When water flows out
of the exhaust hole, reinstall
and tighten the exhaust plug.
8.4 Alarm Reference
NO TICE
● If the Clear button is not displayed on the Details screen of an alarm, the
alarm can be automatically cleared. Such an alarm can be automatically
cleared after the fault is rectified.
● If the Clear button is displayed on the Details screen of an alarm, the alarm
can be manually cleared. Such an alarm is manually cleared by tapping the
Clear button after the fault is rectified.
● The alarm clearance type varies depending on the smart cooling product
model. Some alarms can be cleared automatically and manually. You can clear
alarms based on the site requirements.