Networking
Teamwork
Monitoring
Description
One teamwork network
supports a maximum of 32
smart cooling products. On
the Teamwork Settings
screen of the display modules
of the first and last smart
cooling products, set Enable
teamwork CAN resistor to
Yes.
It takes 3 x
n
seconds to
collect data from
n
smart
cooling products. If the time
required for the host to collect
data from all smart cooling
products does not meet the
performance requirements,
group the smart cooling
products.
● If devices are not grouped
(
n
= 1), set RS485
monitoring grouping to
Enable on the Modbus
Settings screen for each
device.
● If devices are grouped (
n
>
1; recommended:
n
≤ 4),
set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the device with the
COM/FE port connected.
NO TE
● Connect the COM/FE port on the main control module of the last smart cooling product
in each group to the RS485 port on the host.
● Customers can purchase Huawei's ECC and NetEco for the monitoring system.
Figure 4-23 Connecting communications cables
----End
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (FDC Scenario)
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
86