Locatio
n
Display Name
Addre
ss
DIP Switch No.
1
2
3
4
5
6
Hot aisle 4 temp/
humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5 temp/
humid
25
ON
OFF
OFF
ON
ON
OFF
Hot aisle 6 temp/
humid
26
OFF
ON
OFF
ON
ON
OFF
NO TICE
● The default T/H sensor address is 1.
● Keep the last RS485_R DIP switch at OFF.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
4.7 (Optional) Installing Electric Heater Components
and Cables
Electric heater components include the electric heating belt, temperature sensor
probe, and electric heater controller.
Procedure
Step 1 Remove the exhaust side panel.
Step 2 Install the electric heater controller.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
4 System Installation (FDC Scenario)
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
93