Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings to enter the Teamwork
Settings screen.
Figure 6-5 Teamwork setting
Step 2 Set teamwork parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
Table 6-5 Teamwork setting
Parameter
Description
Setting Rule
Teamwork
group No.
The number of the teamwork
group. This parameter should be
the same for all units in the same
teamwork group.
Set the assigned teamwork
group number.
System
address
Smart cooling product addresses
should be different from each
other.
Set the planned teamwork
unit address.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
6 Power-On Commissioning
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
110