Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A296-01
EEV 1 low superheat
degree alarm
EEV 2 low superheat
degree alarm
Major
● The electronic
expansion valve
(EEV) coil is loose.
● The EEV coil is
faulty.
● The cables to the
EEV coil are loose
or damaged.
● The EEV is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Check and maintain
the cables to the
EEV coil.
4. Replace the EEV.
A296-01
Paral comp sys low
superheat degree
alarm
Critical
● The EEV coil is
loose.
● The EEV coil is
faulty.
● The cables to the
EEV coil are loose
or damaged.
● The EEV is faulty.
● The
dehumidification
solenoid valve coil
is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Check and maintain
the cables to the
EEV coil.
4. Replace the EEV.
5. Maintain or replace
the
dehumidification
solenoid valve coil.
A296-02
EEV 1 low superheat
degree alarm
EEV 2 low superheat
degree alarm
Critical
● The EEV coil is
loose.
● The EEV coil is
faulty.
● The EEV is faulty.
● The cables to the
EEV coil are loose
or damaged.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Replace the EEV.
4. Check and maintain
the cables to the
EEV coil.
A296-02
Paral comp sys low
superheat degree
alarm
Critical
● The EEV coil is
loose.
● The EEV coil is
faulty.
● The EEV is faulty.
● The
dehumidification
solenoid valve coil
is faulty.
● The cables to the
EEV coil are loose
or damaged.
1. Reinstall the EEV
coil.
2. Replace the EEV
coil.
3. Replace the EEV.
4. Maintain or replace
the
dehumidification
solenoid valve coil.
5. Check and maintain
the cables to the
EEV coil.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance