Menu
Parameter
Description
Indoor fan
total
runtime
Return air
filter total
runtime
Outdoor
intake air
filter total
runtime
Compressor
total
runtime
EEV total
runtime
Spray pump
total
runtime
Spray
system total
runtime
Exhaust fan
total
runtime
Maint > Sensor
Calibration
Supply air
temp
calibration
value
Sets the calibration value of each sensor
when the detected temperature or
humidity varies from the practical value.
For example, if the detected return air
temperature is 1°C lower than that
detected by other devices, set the
calibration value to 1°C.
Return air
temp
calibration
value
Return air
humidity
calibration
value
Outdoor
intake air
temperature
calibration
value
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
269