2.6 Technical Specifications
Table 2-5 General specifications
Item
Specifications
(Building Scenario)
Specifications (FDC Scenario)
Maximum power
78.5 kW (default power)
Maximum
current
140 A (default current)
Total cooling
capacity
240 kW
1
Sensible cooling
capacity
240 kW
1
Sensible heat
ratio
100%
System
dimensions (H x
W x D)
3600 mm x 2438
mm x 4700 mm
4150 mm x 2438 mm x 6058 mm
Installation
scenario
Indoor
FDC
Power system
380–415 V AC, 3-phase, 50 Hz/60 Hz
Air filter level on
the indoor air
return side (EN
779)
G4
Air filter level on
the outdoor air
intake side (EN
779)
G3
Fan type
EC
Air volume
Indoor: 55,000 m
3
/h
Outdoor: 50,000 m
3
/h
Net weight
5000 kg
11,000 kg
Operating weight 5500 kg
11,500 kg