Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A282-10
Backup power phase
sequence abnormal
Auxiliary cooling
power phase sequence
abnormal
Auxiliary cooling
backup power phase
sequence abnormal
Major
● The power grid is
unstable.
● The phase C input
cable is faulty.
1. Check the power
grid.
2. Rectify the fault of
the phase C input
cable.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
171