Menu
Parameter
Description
Settings > Alarm
Settings >
Compressor
Compressor
liquid pipe
temp sensor
fault
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Settings > Alarm
Settings > Spray
System
Spray water
supply
abnormal
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Spray drain
abnormal
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Settings > System
Settings > Common
Settings
Temperature
and
humidity
control type
This parameter can be set to Cold aisle,
Hot aisle, Return air, or Supply air
based on site requirements. The
temperature and humidity setpoints
corresponding to the selected control
mode are enabled.
Temperature
setpoint
After Temperature and humidity
control type and the temperature value
under this type are set, the device
performs cooling or heating based on the
settings.
Humidity
setpoint
After Temperature and humidity
control type and the humidity value
under this type are set, the device
performs humidifying or dehumidifying
based on the settings.
Cold aisle
sensor*
You can enable or disable the cold aisle
sensors.
Hot aisle
sensor*
You can enable or disable the hot aisle
sensors.
Outdoor
intake air
sensor*
Outdoor intake air sensor* can be set to
Enable or Disable.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
264