Parameter
Description
Return air 1
temperature
sensor fault
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Exhaust air*
temperature
sensor fault
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Supply air
high
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Supply air
low
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Return air
high
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Return air
low
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Cold aisle
high
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Cold aisle
low
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Hot aisle
high
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Hot aisle
low
temperature
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
262