Figure 4-7 Securing the unit
NO TE
This section uses two-layer stacking as an example.
Step 8 Close the maintenance door after the unit is secured.
----End
4.3.3 Checking the Refrigerant
Procedure
Step 1 Remove the adjustable side panels for the compressor.
Step 2 Check whether any of the needle valve bonnets shown in
1. If any bonnet is missing, contact Huawei technical support.
2. If no bonnet is missing, remove the valve bonnets, and press the valve plugs
using the valve bonnets in turn. If gas flows out, the system is normal. If no
gas flows out, contact Huawei technical support.