ADU Error Messages
HP Servers Troubleshooting Guide
D-21
HP CONFIDENTIAL
Writer: Ted Weiman File Name: k-appd ADU Error Messages.doc
Codename: Generic TSG Part Number: 161759-007 Last Saved On: 11/19/02 9:53 AM
Table D-1: Array Diagnostic Utility (ADU) Error Messages
continued
Message Description
Recommended
Action
Swapped cables or
Configuration error detected.
The configuration information
on the attached drives is not
backward compatible with this
controller’s firmware.
SOLUTION: Upgrade the
firmware on this controller. If
this doesn’t solve the problem
then power down system then
move drives back to the
original controller.
The current firmware version
on the controller cannot
interpret the configuration
information on the connected
drives.
Upgrade the firmware.
-Or-
If that does not solve the
problem, move the drives to
the original controller.
Swapped cables or
Configuration error detected.
The maximum logical volume
count
X
was exceeded during
logical volume addition. All
logical volumes beyond
X
have been lost and cannot be
recovered.
SOLUTION: Identify the drives
that contain the lost logical
volumes. Move those drives to
another controller where the
logical volumes can be
recreated. NOTE! If a drive
contains a valid logical volume
and a lost logical volume, then
do not move that drive to
another controller.
More logical drives were
created than are supported on
this controller, causing lost
logical drive volumes.
Identify the drives containing
lost volumes, and then move
them to another controller so
the lost volumes can be
recreated.
WARNING:
Do not move a
drive if it also contains valid
volume data. This process
causes all valid data to be
destroyed.
continued