
SCS Series Manual —
P/N 15712:L 7/18/16
75
Programming
The SCS⁄SCE
3.
Monitor and control modules must be wired on the panel SLC as illustrated in Section 5 “Ratings and Wiring Diagrams” of this manual,
addressed and programmed as non-silenceable as described in the panel manual. The following Software Type IDs must be used.
When the SCS modules are installed and configured, worksheets are filled out, SLC wiring is complete, and monitor and control modules
have been addressed and given the proper Software Type IDs, the programmer must:
•
map each “needed” annunciator point to the proper control module or monitor module by creating a user-defined group. “Unneeded”
annunciator points require no mapping.
•
map each “unused” annunciator point to a valid unused control point that will not be activated by any CBE and is programmed as non-
silenceable. N000L01M001 can be used as the valid unused control point. NOTE: When FSCS mode is used for NCA smoke control
modules, use
only
N000L01M001 to program each “unused” annunciator point in ACS programming.
Refer to Figure 3.29 and Figure 3.31 and accompanying text for instructions.
•
FSCS mode only - map annunciator points from 65 through 96 to a panel smoke control zone or device as needed.
Programming may be done for the NFS2-3030 by using the panel keypad, the network annunciator keypad, or the Veri•Fire Programming
Utility. Programming may be done for the NFS-320/NFS2-640 by using the NCA-2 keypad or the Veri•Fire Programming Utility.
3.9.2 NFS2-3030 and NCA-2/NFS2-640/NFS-320 Programming
Using the NFS2-3030 or NCA-2 keypad, enter ACS Programming (refer to Figure 3.30). Move the cursor between fields with the arrows on
the keyboard. When the cursor is in the proper address field, press the soft keys as described below.
Type of Device
Software Type ID
Control Relay Module
RELAY or NONRESET CTL*
Monitor Module
NON FIRE
*Use NONRESET CTL only in HVAC mode without CBE lockout
A C S P R O G R A M M I N G
A 0 1 : U D A C T
A 0 2 : F S C S
A 0 3 : 9 6 P T
A 0 4 : T M 4
A 0 5 : N O
A 0 6 : N O
A 0 7 : N O
A 0 8 : N O
A 0 9 : N O
A 1 0 : N O
A 1 1 : N O
A 1 2 : N O
A 1 3 : N O
A 1 4 : N O
A 1 5 : N O
A 1 6 : N O
A 1 7 : N O
A 1 8 : N O
A 1 9 : N O
A 2 0 : N O
A 2 1 : N O
A 2 2 : N O
A 2 3 : N O
A 2 4 : N O
A 2 5 : N O
A 2 6 : N O
A 2 7 : N O
A 2 8 : N O
A 2 9 : N O
A 3 0 : N O
A 3 1 : N O
A 3 2 : N O
A N N U N C I A T O R T Y P E
A C C E P T
P O I N T P R O G R A M M I N G
B A C K
Annunciator
Address 2
field set to
FSCS
POINT PROGRAMMING soft key
ACCEPT soft key
ANNUNCIATOR
TYPE soft key