106
SCS Series Manual —
P/N 15712:L 7/18/16
Restrictions
Testing
•
program the associated annunciator points (33 through 64) as software type ACON for the respective SCS address
(AM2020/AFP1010).
•
program the associated annunciator points (33 through 64) to any unused control point (NFS2-3030, NFS2-640, NFS-320)
•
program the associated annunciator points (33 through 64), using ACS programming, to the source N000L01M001 when smoke control
modules are on an NCA or NCA-2 in FSCS mode.
All inputs that will initiate smoke control:
•
must be mapped to Z240 (AM2020/AFP1010 only, Version 4.0 and higher).
•
must be mapped to an NFS2-3030 or NCA-2 annunciator address from 6 through 96.
If one or more of the four annunciator points are not selected for any toggle switch groups (unneeded), do not install the respective annunci-
ator point address(es).
For AM2020/AFP1010/INA only: When using software type ID AFCM for a CON
ON⁄OP
or CON
OFF⁄CL
protocol point, the software type ID
for the appropriate control module must be FRCM. When using the software type ID NOA for smoke control applications, the tracking
option for the respective monitor module must be enabled.
When changing functions of a switch group, and subsequently the protocol points, make sure to install those points that were previously
unneeded and remove those points that were previously needed.
When programming Control Modules for smoke control applications, the Walk Test option must be disabled and the Signal Silence option
must be enabled.
4.5 Testing
Dedicated Systems require weekly automatic testing by the FACP.
NOTE:
1. Software Part Numbers 73631 and 73845 are not compatible with INA combinations after M2.7.
2. Part #SCSV2.84 is not compatible with FACP/INA combinations prior to M2.8.
3. NFS-320s, NFS2-640s, NFS-640s, NFS2-3030s, NFS-3030s, NCAs and NCA-2s are only compatible with
software #SCS2.84 or higher. (They are not compatible with any 73XXX series software versions.)
4. To use the SCS V4.0, NFS2-3030, and/or NCA-2 must be running software V21 or higher.