SCS Series Manual —
P/N 15712:L 7/18/16
195
Size Limitations
AM2020/AFP1010 Control-By-Event
Examples:
1.
The following Control-By-Event takes up 13 bytes in memory:
2.
The following CBE takes up 11 bytes in memory:
Due to the 14-byte size limitation, it may be necessary to use more than one Equation or List to accomplish a desired result. Through the use
of reverse activating zones, an equation which normally would contain too many bytes can be broken up into several smaller equations.
In the example below, a control module is to be activated by any one of 14 software zones:
CBE Equation for
L1M1
:
OR( Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9 Z10 Z11 Z12 Z13 Z14 )
1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 + 1 = 16 Bytes
(too many)
OR(
Z1
Z4
Z9
Z16
Z23
L1D3
L2M7
)
Size in bytes
1
+ 1
+ 1
+ 1
+ 1
+ 1
+ 3
+ 3
+ 1
= 13
DEL(
00.00.30 00.01.30
(
Z1
)
)
Size in bytes
1
+ 6
+1
+1
+1
+1
=
11
Z4
Z5
Z2
Z7
Z8
Z13
Z10
Z11
Z3
Z6
Z14
Z1
Z9
Z12
L1M1