SCS Series Manual —
P/N 15712:L 7/18/16
67
Configuration
The SCS⁄SCE
1
No Function - Factory Setting
The SCE will not function with dipswitches selected
as shown on the right. This is a factory setting that
must be changed in order for the SCS to function
properly.
2
When used with an SCE, all 16 switch groups are
available for group type 1 operation. Type 1 switch
groups require one monitor module. Type 1 switch
groups can be used for fans or dampers. The monitor
module is used for the OFF verification of the fan.
3
When used with an SCE, all 16 switch groups are
available for group type 2 operation. Type 2 switch
groups require one monitor module. Type 2 switch
groups can be used for fans or dampers. The monitor
module is used for the ON verification of the fan.
4
When used with an SCE, all 16 switch groups are
available for group type 3 operation. Type 3 switch
groups require two monitor modules. Type 3 switch
groups are usually only used for dampers. One
monitor module is used for the OPEN verification of
the damper and the other monitor module is used for the CLOSED verification of the damper.
5
When used with an SCE, all 16 switch groups are
available for group type 4 operation. Type 4 switch
groups require one control module. Type 4 switch
groups can be used for fans or dampers. The control
module is used for OFF control of a fan.
6
When used with an SCE, all 16 switch groups are
available for group type 5 operation. Type 5 switch
groups require one control module and one monitor
module. Type 5 switch groups can be used for fans or
dampers. The control module is used for OFF control
of a fan and the monitor module is used for the OFF verification of the fan.
7
When used with an SCE, all 16 switch groups are
available for group type 6 operation. Type 6 switch
groups require one control module and one monitor
module. Type 6 switch groups can be used for fans or
dampers. The control module is used for OFF control
of a fan and the monitor module is used for the ON verification of the fan.
Table 3.10 HVAC Mode Dipswitch Settings (1 of 5)
OFF
ON
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SCS-8
SCE-8
OFF
ON
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
SCS-8
SCE-8
OFF
ON
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
SCS-8
SCE-8
OFF
ON
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
SCS-8
SCE-8
OFF
ON
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
SCS-8
SCE-8
OFF
ON
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
SCS-8
SCE-8
OFF
ON