Chapter IV Function Parameter Table
96
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
the operating current is greater than the
motor stall current then after the motor
stall time the drive displays E018 alarm.
FE.05
Accelerati
on and
deceleratio
n
frequency
switching
point
Setting range: lower limit frequency ~
upper limit frequency
When the running frequency is greater
than FE.05, use F2.14 and F2.15 for
acceleration and deceleration.
When it is less than FE.05, use F1.11
and F1.12 for acceleration and
deceleration.
0.01Hz
50.00Hz
×
FE.06
Pump
cleaning
repetitions
FE.06 setting range: 0
~
100
FE.07 setting range: lower limit frequency
~ upper limit frequency
FE.08 setting range: 0.0
~
6000.0s
When the FE.06 is 0, the water pump
cleaning is disabled.
FE.07 Set the operational frequency for
pump cleaning.
A wave crest runs at FE.07 for FE.08
seconds
1
0
×
FE.07
Pump
cleaning
frequency
0.01Hz
10.00Hz
×
FE.08
Pump
cleaning
time
0.1s
6.0s
×
FE.09
Frost
Protection
/ Defrost
function
Setting range: 00
~
11
LED unit digit: Frost protection
0: disable
1: enable
LED ten digits: Defrost function
0: disable
1: enable
1
0
×
FE.10
Defrost
operating
frequency FE.10 Setting range: lower limit
frequency ~ upper limit frequency
FE.11 setting range: 0.0
~
6000.0s
FE.12 setting range: 0.0
~
6000.0s
Every FE.12 seconds, run at FE.10
frequency for FE.11 seconds.
0.01Hz
8.00Hz
×
FE.11
Defrost
running
time
0.1s
60.0s
×
FE.12
Defrost
operation
interval
0.1s
300.0s
×
FE.13
Defrost
braking
FE.13 Setting range: 0.0
~
100.0% drive’s
rated current
0.1%
100.0%
×