Chapter V Basic Operation Instructions
135
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
F8.13
Gain
switching
threshold
Set range: 0.0
~
100.0%
0.1%
0.0%
○
F8.14
PID
sampling
period
Set range: 1
~
60000ms
1ms
1ms
○
F8.15
Deviation
limit
Set range: 0.0
~
50.0%
0.1%
0.0%
○
F8.16
Closed-loo
p regulation
features
0: Positive action
1: Negative action
1
0
○
F8.17
PID initial
value
F8.17 set range: 0.0
~
100.0%
F8.18 set range: 0.00
~
600.00s
0.1%
0.0%
×
F8.18
PID initial
value hold
time
0.01s
0.00s
×
F8.19
Closed-loo
p output
polarity
selection
0: Closed-loop output is negative, run at
zero-frequency
1: Closed-loop output is negative, reverse
1
0
○
F8.20
PID reverse
cutoff
frequency
Set range: 0.00~upper limit frequency
0.01Hz 2.00Hz
×
F8.21
PID
feedback
loss
detection
value
F8.21 set range: 0.0
~
100.0%
F8.22 set range: 0.0
~
200.0s (0.0s indicates
no detection)
0.1%
10.0%
○
F8.22
PID
feedback
loss
detection
time
0.1s
0.0s
○
F8.23
Maximum
sensor
range
Set range: 0.0
~
200.0bar
0.1bar
10.0bar
○
F8.24
Water
supply
sleep
selection
0: Automatic sleep
1: Run at lower limit frequency
1
0
○
F8.25
Water
supply
sleep
detection
time
F8.25 set range: 0.0
~
3600.0s
F8.26 set range: 0.01
~
600.00s
0.1s
2.0s
○
F8.26
Water
supply
sleep
deceleratio
n time
0.01s
30.00s
○