Chapter IV Function Parameter Table
46
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
Note: For safety, be cautious when
setting to 1.
F2.07
Start
protection
wait time
Set range: 0.0
~
10.0s
0.1s
0.0s
○
F2.08
Stop mode
0: Deceleration stop: After receiving the
stop command, the drive will gradually
reduce the output frequency according to
the deceleration time, and stop when the
frequency reaches to zero.
1: Free running stop: After receiving the
stop command, the drive immediately
stops the output, and the load stops freely
according to the mechanical inertia.
2: Deceleration stop + DC braking: After
receiving the stop command, the drive
reduces the output frequency according to
the deceleration time, and starts the DC
braking when reaching the stop braking
start frequency.
1
0
×
F2.09
DC
braking
start
frequency
at stop
F2.09 set range: 0.00
~
60.00Hz
F2.10 set range: 0.00
~
10.00s
F2.11 set range: 0.0
~
150.0% drive rated
current
F2.12 set range: 0.0
~
60.0S (0.0 indicates
the DC braking does not act)
F2.13 set range: 0
~
1
1. DC braking start frequency at stop:
Means that the drive starts DC braking
when reaching this frequency during the
deceleration stop.
2. DC braking wait time at stop: During
decelerating and stopping, the time
interval from the moment when the
operation frequency reaches the start
frequency of braking to the moment when
the DC braking is applied.
3. DC braking current at stop: Refers to
the DC braking amount that added. The
larger the current, the stronger the DC
0.01Hz
0.00Hz
○
F2.10
DC
braking
wait time
at stop
0.01s
0.10s
○
F2.11
DC
braking
current at
stop
0.1%
100.0%
○
F2.12
DC
braking
time at
stop
0.1s
0.0s
○