Chapter IV Function Parameter Table
85
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
automatically.
2. Fault automatic reset interval time:
Select the time interval from the fault
occurrence to the automatic reset action.
3. Within 2 minutes after the drive
operates, if there is no fault, it will
automatically clear the number of resets,
and accumulate the number of resets from
the beginning.
4. When the number of automatic resets is
set to 0, it indicates that automatic reset is
prohibited and fault protection is
performed immediately.
Note: The drive module protection
(E010) and external equipment failure
(E015) have no automatic reset
function. After the automatic reset is
completed, it will automatically start
and run at the speed tracking. Use the
automatic fault reset function with
caution, otherwise, it may cause
personal injuries and property losses.
FA.09
Automatic
reset
interval
time
0.1s
5.0s
×
FA.10
Wave-by-
wave
current
limiting
points
setting
FA.10 set range: 0.0~250.0% (0.0%
indicates there is no wave-by-wave
current limiting function)
FA.11 set range: 0~60000 ms (0 ms
indicates no fault alarm function of
wave-by-wave current limiting)
When the output current is greater than
the wave-by-wave current limiting point
set by FA.10, perform wave-by-wave
current limiting, and when the current
limiting time exceeds the wave-by-wave
current limiting time set by FA.11, report
the E029 fault.
0.1%
0.0%
×
FA.11
Wave-by-
wave
current
limiting
time
1ms
0ms
×
FA.12
Delay time
of
abnormal
protection
of buffer
circuit
Set range: 0.0~20.0s (0.0s indicates no
detection function for abnormal buffer
circuit)
In the running state, if the buffer circuit is
abnormal and exceeds the delay time set
by FA.12, report the E026 fault.
0.1s
1.0s
○
FA.13
Reserved -
-
-
*