Chapter IV Function Parameter Table
53
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F5.16
Reserved -
-
-
*
F5.17
Reserved -
-
-
*
F5.18
Analog
automatic
zero drift
adjustment
Set range: 0
~
1
When set to 1, the automatic zero drift
adjustment of the analog quantity must be
performed. It must be ensured that there is
no external analog input quantity input.
0
0
○
F5.19
PULSE
minimum
input
0.00
~
F5.21
0.01KHz 0.00KHz
○
F5.20
Correspon
ding
setting of
PULSE
minimum
input
-100.0%
~
100.0%
0.1%
0.0%
○
F5.21
PULSE
maximum
input
F5.19
~
50.00KHz
0.01KHz 50.00KHz
○
F5.22
Correspon
ding
setting of
PULSE
maximum
input
-100.0%
~
100.0%
0.1%
100.0%
○
F5.23
PULSE
filter time 0
~
1000ms
1ms
10ms
○
F5.24
HDO
function
selection
0: Running frequency (0
~
Maximum
output frequency)
1: Set frequency (0
~
Maximum output
frequency)
2: Output current (0
~
2 times rated
current)
3: Output torque (0
~
2 times rated torque)
4: Output voltage (0
~
1.2 times rated
voltage)
5: Bus voltage (0
~
1000V)
6: AI1 (0
~
10V/0
~
20mA)
7: AI2 (0
~
10V/0
~
20mA)
8: Reserved
9: Output power (0
~
2 times rated
frequency)
10: Pulse input (0
~
50.00KHz)
11: Communication setting (0
~
F1.06)
12: Operating frequency after
compensation (0
~
maximum output
frequency)
1
5
○
F5.25
AO1
function
selection
1
0
○
F5.26
AO2
function
selection
1
1
○
F5.27
HDO
output
lower limit
F5.27 set range: 0.0
~
F5.29
F5.28 set range: 0.00
~
50.00KHz
0.1%
0.0%
○