Chapter V Basic Operation Instructions
120
Output function description:
Set value
Function
Description
0
No output
The output terminal has no function.
1
Drive running signal
(RUN)
The drive is under the running status and outputs an indication
signal.
2
Frequency arrival
signal (FAR)
Refer to the function description of F6.18.
3
Frequency level
detection signal
(FDT1)
Refer to the function description of F6.14
~
F6.15.
4
Frequency level
detection signal
(FDT2)
Refer to the function description of F6.16
~
F6.17.
5
Overload detection
signal(OL)
If the output current of the drive exceeds the FA.15 overload
detection level, it outputs an indication signal after FA.16
overload detection time.
6
Undervoltage lockout
stopping (LU)
When the DC bus voltage is lower than the undervoltage limit
level, an indication signal is output, and the LED displays
“P.oFF”.
7
External fault stop
(EXT)
When the drive has an external fault trip alarm (E015), it
outputs an indication signal.
8
Frequency upper limit
(FHL)
When the set frequency ≥ the upper limit frequency and the
operation frequency reaches the upper limit, an indication
signal is output.
9
Frequency lower limit
(FLL)
When the set frequency ≤ the lower limit frequency and the
operation frequency reaches the lower limit, an indication
signal is output.
10
Drive running at zero
frequency
When the drive output frequency is less than or equal to FC.10
zero frequency arrival range, and under the operation status, an
indication signal is output.
11
PLC phase running
completion
After the simple PLC phase operation is completed, an
indication signal (single pulse signal, width 250ms) is output.
12
PLC cycle completion After the simple PLC completes one operation cycle, an
indication signal (single pulse signal, width 250ms) is output.