Chapter V Basic Operation Instructions
118
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
(level)
26: Immediate DC braking
27: UP/DOWN setting cleared
28: Control command switched to keypad
29: Control command switched to terminal
30: Control command switched to
communication
31: Frequency source switched to the main
frequency X
32: Frequency source switched to auxiliary
frequency Y
33: High-frequency pulse count reset
34
:
Reserved
35
:
Water shortage fault
36
:
Reserved
37
:
Reserved
38
:
Fire override mode
39
:
Pump A maintenance signal
40
:
Pump B maintenance signal
41
:
Pump C maintenance signal
F6.03
Function
selection
of
multi-funct
ion input
terminal
DI4
12
F6.04
Function
selection
of
multi-funct
ion input
terminal
DI5
13
F6.19
HDI
terminal
input mode
selection
(DI5)
0: Switch input
1: High-frequency pulse input (see F5.19
~
F5.23)
1
0
×
F6.24
DI input
switch
polarity 1
00000~11111
LED single digit: DI1 positive/negative
logic definition
LED tens digit: DI2 positive/negative logic
definition
LED hundreds digit: DI3 positive/negative
logic definition
LED thousands digit: DI4 positive/negative
logic definition
LED 10 thousands digit: DI5
positive/negative logic definition
11111
11111
○
F6.28
DI filter
time
0
~
1000ms
1ms
5ms
○
Fd.00
VDI1
terminal
function
selection
Same as F6.00
~
F6.08 function code
setting.
1
0
×
Fd.01
VDI2
terminal
function
selection
1
0
×