Chapter IV Function Parameter Table
75
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
rewinding tension PID control.
1: Negative action. When the feedback
signal is less than the input quantity, the
output frequency of the drive drops to
make the PID reach balance. Such as
unwinding tension PID control.
F8.17
PID initial
value
F8.17 set range: 0.0
~
100.0%
F8.18 set range: 0.00
~
600.00s
1. After the drive starts, accelerate to the
initial PID value (F8.17) according to the
acceleration time. After running for a
period of time at this initial value (F8.18),
the PID starts the closed-loop adjustment
operation.
2. This function allows the closed-loop
adjustment to quickly enter the stable
phase.
0.1%
0.0%
×
F8.18
PID initial
value hold
time
0.01s
0.00s
×
F8.19
Closed-loo
p output
polarity
selection
0: Closed-loop output is negative, run at
zero-frequency
1: Closed-loop output is negative, reverse
1
0
○
F8.20
PID
reverse
cutoff
frequency
Set range: 0.00~upper limit frequency
When the PID output frequency is
negative (i.e. the drive reverses),
determine the upper limit of the reverse
frequency.
0.01Hz
2.00Hz
×
F8.21
PID
feedback
loss
detection
value
F8.21 set range: 0.0
~
100.0%
F8.22 set range: 0.0
~
200.0s (0.0s
indicates no detection)
When the feedback value is less than the
feedback loss detection value and the
feedback loss detection time has passed,
the drive reports a closed-loop feedback
loss fault (E020).
0.1%
10.0%
○
F8.22
PID
feedback
loss
detection
time
0.1s
0.0s
○
F8.23
Maximum
sensor
range
Set range: 0.0
~
200.0bar
The maximum range of the sensor
corresponds to the maximum value of the
0.1bar
10.0bar
○