Chapter V Basic Operation Instructions
140
Parameter
Code
Parameter
Name
Parameter detailed description
Minimum
Unit
Factory
Value Change
loss
detection
time
F8.23
Maximum
sensor
range
Set range: 0.0
~
200.0bar
0.1bar 10.0bar
○
F8.24
Water
supply
sleep
selection
0: Automatic sleep
1: Run at lower limit frequency
1
0
○
F8.25
Water
supply
sleep
detection
time
F8.25 set range: 0.0
~
3600.0s
F8.26 set range: 0.01
~
600.00s
0.1s
2.0s
○
F8.26
Water
supply
sleep
deceleratio
n time
0.01s
30.00s
○
F8.27
Water
supply
wake
pressure
tolerance
F8.27 set range: 0.0
~
100.0% (100.0% is
the set pressure value)
F8.28 set range: 0.0
~
3600.0s
0.1%
10.0%
○
F8.28
Water
supply
wake
detection
time
0.1s
2.0s
○
F8.29
Water
pressure
overpressur
e alarm
detection
value
Set range: 0.0
~
100.0% (Do not test when
set to 0, 100.0% is the maximum range of
pressure sensor)
0.1%
90.0%
○
F8.30
Water
pressure
undervoltag
e alarm
detection
value
Set range: 0.0
~
100.0% (Do not test when
set to 0, 100.0% is the maximum range of
pressure sensor)
0.1%
0.0%
○
F8.31
Water
pressure
abnormal
alarm
detection
time
Set range: 0.0
~
3600.0s
0.1s
50.0s
○
F8.32
Water
shortage
F8.32 set range: 0.0
~
100.0% (100.0% is
the set pressure value)
0.1%
0.0%
○