Chapter IV Function Parameter Table
38
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
through group F9 function code.
8: PID input, the drive operation mode is
process PID control, and the operation
frequency is the frequency value after PID
action. In this case, you need to set PID
related functions through group F8.
9-15: Reserved
F1.04
Frequency
source
combinati
on mode
0: X, the current frequency is set to the
main frequency X.
1: Y, the current frequency is set to the
auxiliary frequency Y.
2: X+Y, the current frequency is set to the
main frequency X + the auxiliary
frequency Y.
3: X-Y, the current frequency is set to the
main frequency X - the auxiliary
frequency Y.
4: Max (X,Y). The larger of the main
frequency X and the auxiliary frequency
Y is the set frequency.
5: Min (X,Y). The smaller of the main
frequency X and the auxiliary frequency
Y is the set frequency.
Note: If the X and Y directions are not
the same, the frequency direction after
the combination of 2 and 3 is based on
the main frequency X, while 4 and 5 is
based on the selected frequency
direction. Besides the calculation
during combination is based on the
absolute value of the main and
auxiliary frequencies, if the calculated
value is less than 0, it will run at zero
frequency.
The combination mode can be switched
through the multifunctional input
terminal (group F6).
1
0
○
F1.05
Digital
setting of
auxiliary
frequency
Y
Set range: Lower limit frequency~upper
limit frequency
When the auxiliary frequency Y input
channel is selected to “digital setting 1”,
this function code value is the frequency
set value of the auxiliary frequency Y.
0.01Hz
50.00Hz
○
F1.06
Maximum
output
frequency
Set range: Upper limit frequency
~
650.00Hz
0.01Hz
50.00Hz
×