Chapter IV Function Parameter Table
61
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
the motor. The REV terminal determines
the operation direction. When the drive
stops, the Sin terminal must be
disconnected to complete the stop.
F6.10
UP/DN
rate
0.01
~
99.99Hz/s
This function code defines the change rate
of the set frequency modified by the
UP/DN terminal.
0.01Hz/s 1.00Hz/s
○
F6.11
Open
collector
output
terminal
DO1
0: No output
1: Drive running signal (RUN)
2: Frequency arrival signal (FAR)
3: Frequency level detection signal
(FDT1)
4: Frequency level detection signal
(FDT2)
5: Overload detection signal(OL)
6: Undervoltage lockout stopping (LU)
7: External fault stop (EXT)
8: Frequency upper limit (FHL)
9: Frequency lower limit (FLL)
10: Drive running at zero frequency
11: PLC phase running completion
12: PLC cycle completion
13: Set count value arrival
14: Specified count value arrival
15: Set length arrival
16: Drive ready to run (RDY)
17: Drive fault
18: Reserved
19: Set cumulative running time arrival
20: Forward running
21: Reverse running
22: Reserved
23: Water supply sleep running indication
24: Water pipe overpressure indication
25: Water pipe under-pressure indication
26: Water pipe shortage indication
27: Water tank shortage indication
1
0
×
F6.12
Open
collector
output
terminal
DO (HDO
terminal)
1
1
×