Chapter IV Function Parameter Table
62
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
28:Water pipe break indication
Detailed description of terminal functions:
1: Drive running signal (RUN): Outputs
an indication signal id the drive is
running.
2: Frequency arrival signal (FAR): Refer
to the function description of F6.18.
3: Frequency level detection signal
(FDT1): Refer to the function description
of F6.14
~
F6.15.
4: Frequency level detection signal
(FDT2): Refer to the function description
of F6.16
~
F6.17.
5: Overload detection signal (OL): If the
output current of the drive exceeds the
FA.15 overload detection level, it outputs
an indication signal after FA.16 overload
detection time.
6: Undervoltage lockout stopping (LU):
When the DC bus voltage is lower than
the under-voltage limit level, it outputs an
indication signal, and the LED displays
“P.oFF”
7: External fault stop (EXT): When the
drive has an external fault trip alarm
(E015), it outputs an indication signal.
8: Frequency upper limit (FHL): When
the set frequency ≥ the upper limit
frequency and the operation frequency
reaches the upper limit; an indication
signal is output.
9: Frequency lower limit (FLL): When the
set frequency ≤ the lower limit frequency
and the operation frequency reaches the
lower limit; an indication signal is output.
10: Drive running at zero frequency:
Output frequency ≤ FC.10 zero frequency
arrival range, it outputs an indication
signal under operation status.
11: PLC phase operation completed: After
a single stage of simple PLC operation is
completed, an indication signal (single
pulse signal, width is 250ms) is output.
12: PLC cycle completed: After the
simple PLC completes one complete
cycle, an indication signal (single pulse
signal, width is 250ms) is output.
13: Set count value arrival
14: Specified count value arrival
For functions 13~14, refer to F6.22~F6.23
function description.
15: Set length arrival: When the actual
length U0.15≥FC.11 set length, an
F6.13
Relay
output
function
(TA/TB/T
C)
1
17
×