Chapter IV Function Parameter Table
52
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F5.11 set range: 0
~
1000ms
1. The function code defines the
relationship between the analog input
voltage and the corresponding set value of
the analog input. When the analog input
voltage exceeds the set maximum or
minimum input range, it will be
calculated with the maximum or
minimum input.
2. When analog input is current input, a
current of 0
~
20mA
corresponds to a voltage of 0
~
10V.
3. In different applications,
the nominal values corresponding to the
analog setting 100.0% are different,
please refer to the instructions of
applications for details. The following
legend illustrates the different settings:
4. Filter time of analog input: Adjust the
sensitivity of the analog input. Increasing
this value appropriately can enhance the
anti-interference of the analog quantity,
but will weaken the sensitivity of the
analog input.
5. Analog zero drift setting: Generally,
there will be some zero drift in the analog
quantity. On some occasions with high
accuracy requirements, the zero drift
setting will achieve a better corresponding
effect.
Note: Analog AI1 supports
0~10V/0~20mA input (selected by
jumper J1), and analog AI2 supports
0~10V/0~20mA input (selected by
jumper J2).
F5.03
Set value
correspond
ing to AI1
maximum
value
0.1%
100.0%
○
F5.04
AI1 zero
drift
setting
0.01V
0.00V
○
F5.05
AI1 filter
time
1ms
10ms
○
F5.06
AI2
minimum
value
0.01V
0.00V
○
F5.07
Set value
correspond
ing to AI2
minimum
value
0.1%
0.0%
○
F5.08
AI2
maximum
value
0.01V
10.00V
○
F5.09
Set value
correspond
ing to AI2
maximum
value
0.1%
100.0%
○
F5.10
AI2 zero
drift
setting
0.01V
0.00V
○
F5.11
AI2 filter
time
1ms
10ms
○
F5.12
Reserved -
-
-
*
F5.13
Reserved -
-
-
*
F5.14
Reserved -
-
-
*
F5.15