Chapter IV Function Parameter Table
64
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F6.14
FDT1
level
F6.14 set range: 0.00
~
650.00Hz
F6.15 set range: 0.00
~
650.00Hz
F6.16 set range: 0.00
~
650.00Hz
F6.17 set range: 0.00
~
650.00Hz
F6.14
~
F6.15 are supplementary
definitions for No. 3 function FDT1 in the
terminal output function, F6.16
~
F6.17
are supplementary definitions for No. 4
function FDT2 in the terminal output
function. The usage of both is the same.
In the following, In the below example,
F6.14
~
F6.15 are taken as an example:
When the output frequency is greater than
or equal to a certain set frequency (FDT1
level), it outputs an indication signal until
the output frequency drops to a frequency
(FDT1 level - FDT1 lag) lower than
FDT1 level, as shown in the figure.
0.01Hz
50.00Hz
○
F6.15
FDT1 lag
0.01Hz
1.00Hz
○
F6.16
FDT2
level
0.01Hz
25.00Hz
○
F6.17
FDT2 lag
0.01Hz
1.00Hz
○
F6.18
Frequency
arrival
(FAR)
detection
width
0.00
~
650.00Hz
This parameter is a supplementary
definition for No. 2 function in the
terminal output function. As shown in the
figure, when the output frequency of the
drive is within the positive and negative
detection widths of the set frequency, a
pulse signal is output.
0.01Hz
2.50Hz
○
F6.19
HDI
terminal
input
0: Switch input
1: High-frequency pulse input (see
F5.19
~
F5.23)
1
0
×